Three-phase electrical panel ade-rs 0.5-3/23 lcd/rs
Payment methods
COMPOSITION:
- ABS box (type V0)
- Door lock switch-disconnector
- Mother board
- LCD panel board
- Fuses (Pos. 01, 02, and 03)
- Circuit breaker (Pos. 04 and 05)
- Cable glands
- Mounting brackets
- Instruction booklet.
TECHNICAL CHARACTERISTICS:
- Supply voltage 230 Vac ±10%.
- Working frequency: 50/60 Hz
- Degree of protection: IP55
- Operating temperature: -5 / +40°C
- Automatic-0-Manual operation key
- Start-Stop key
- Reset key
- Keys for parameter settings
- Acoustic annunciator (buzzer)
- Liquid crystal display for displaying:
- Mains voltage; - Motor current; - Motor cosφ; - Motor power; - Pressure; - Level; - Motor status; - Digital inputs status; - Level probes status; - Alarms (last 5 of which are in memory); - Motor operating hours; - All messages related to motor operation; - Multilingual: Italian, English, Spanish, German, French.
- 2 extra-low voltage inputs for pressure switches or floats (dry contacts).
- 4 inputs for electroprobes plus common probe, with adjustable sensitivity from 0 to 50 kΩ (trimmer) with fill/empty function
- Input for 4-20mA sensor
- RS485 for MODBUS-RTU with possible termination
- WI-FI wireless module with dedicated APP for smartphones
- Aux output for alarm
PROTECTIONS:
- Minimum/maximum voltage
- Minimum, maximum or no load and unbalance current
- Dry run among the following options:
- Pressure (transducer); - Minimum current; - Cosφ; - Level (probes or floats).
- Fuse or circuit breaker for power circuit protection Electronic board protection fuses.
SETTINGS AND CONTROLS:
- Language
- Mains re-entry delay
- Minimum voltage
- Maximum voltage
- Minimum current (dry run)
- Maximum current (overload)
- Dry run delay
- Dry run restore delay
- No. of dry run restore attempts
- Thermal delay
- Thermal reset delay
- No. of attempts thermal restoration
- Minimum cosφ;
- Hour meter
- Digital application selection (probes, floats, pressure switches)
- Analog application selection (transducer) - Sensor type (pressure or level); - Sensor pressure; - Maximum pressure; - Dry running pressure; - Dry running delay; - Filling delay; - Emptying/filling mode; - Alarm level; - Minimum level; - Maximum level.
- Automatic reset mode
- Self-configuration
- Probe sensitivity: 5 to 120 kΩ
- BRAND
- FLORIDA
- POWER (Kw)
- ALIMENTATION (V.)
- 400
- CORRENTE D'IMPIEGO
Services that makes difference
24/48H shipping
Ultra-fast shipping with express courier, to offer excellent and timely service to our customers.
Secure payments
We ensure maximum security in online payments through advanced transaction protection systems for the peace of mind of our customers.
Pay in 3 installments with PayPal
Choose the convenience of paying in three interest-free installments with PayPal. An option designed for your financial flexibility.